120
V Model Specifications |
| |
| GENERAL |
|
| Rated
Capacity: |
700VA,
1000 VA, 1500 VA, 2000 VA, 3000 VA with a power factor
of 0.7 |
| Technology: |
True
on-line, double conversion topology with integral automatic
bypass |
| INPUT |
|
| Phase:
|
Single
phase plus ground |
| Input
Voltage Range: |
100V:
76-130V, 110V: 80-138V, 115V: 83.5-140V, 120V: 87-140V |
| Input
Power factor: |
0.98 |
| Frequency: |
50
/ 60 Hz Auto sensing |
| AC
Frequency range: |
45
- 65 Hz |
| Synchronization
range: |
±
3Hz |
| Input
Current (120V): |
700VA
-5.8A, 1000VA -8.2A, 1500VA -12.4A, 2000VA -16.5A,
3000VA - 25A |
| Input
Protection: |
Circuit
Breaker for overload and short protection |
| DC
Bus Voltage: |
700VA
- 24V, 1000VA - 36V, 1500VA - 48V, 2000VA - 72V, 3000VA
- 96V |
| OUPUT |
|
| Output
Voltage: |
100
/ 110 / 115 / 120 VAC |
| Voltage
regulation: |
±
2% (700VA - 2000VA) ± 3% (3000VA) |
| Voltage
distortion: |
<
5% THD with non-linear loads, < 3% THD with linear
loads |
| Frequency
regulation: |
±
0.25 Hz (while on battery) |
| Dynamic
response: |
±
9 % max from 100% to 20 % or from 20% to 100 % linear
load |
| Overload
capacity: |
105%
for 10 seconds, 130% ± 10% for 300 msec |
| Efficiency
(Bypass Mode): |
Greater
than 95% |
| Efficiency
(On-line Mode): |
Greater
than 88% |
| Crest
Factor: |
3
: 1 |
| 120
V TOWER MODELS |
Capacity |
740VA
/490 W |
1000VA
/ 700 W |
1500VA
/ 1050 W |
2000VA
/ 1400 W |
3000VA
/ 2100 W |
| Input
Connection |
Fixed
power cord |
Hardwire
Terminals |
| Output
Connection |
4x
NEMA 5-15R |
8
x NEMA 5-15 R
+ Hardwire Terminals |
| Battery
Type & Rating |
Sealed,
lead-acid
7.2Ah/12V |
Sealed,
lead-acid
7.2Ah/12V |
Sealed,
lead-acid
7.2Ah/12V |
Sealed,
lead-acid
7.2Ah/12V |
Sealed,
lead-acid
7.2Ah/12V |
| Battery
Quantity |
2 |
3 |
4 |
6 |
8 |
| Backup
Time (full load) |
6
min |
8
min |
7
min |
8
min |
7
min |
| Recharge
Time |
<8
hours to 90 % |
Dimensions
ins/mm
W x D x H |
5.7
x 15.8 x 8.7
145 x 400 x 220 |
7.7
x 18.5 x 15.2
195 x 470 x 385
|
| Weight
lbs/kg (net) |
27.5 /
12.5 |
33 / 15 |
39.6 /
18 |
70.4 /
32 |
81.4 /
37 |
| 120
V 19" RACK-MOUNT MODELS (3U) |
Capacity |
740VA
/490 W |
1000VA
/ 700 W |
1500VA
/ 1050 W |
2000VA
/ 1400 W |
3000VA
/ 2100 W |
| Input
Connection |
Fixed
power cord
|
| Output
Connection |
6
x NEMA 5-15R |
4
x NEMA 5-15 R |
| Battery
Type & Rating |
Sealed,
lead-acid
7.2Ah/12V |
Sealed,
lead-acid
7.2Ah/12V |
Sealed,
lead-acid
7.2Ah/12V |
Sealed,
lead-acid
7.2Ah/12V |
Sealed,
lead-acid
7.2Ah/12V |
| Battery
Quantity |
2 |
3 |
4 |
6 |
8 |
| Backup
Time (full load) |
6
min |
8
min |
7
min |
6
min |
5
min |
| Recharge
Time |
<8
hours to 90 % |
Dimensions
ins/mm
W x D x H |
19
x 15.8 x 5.2
485 x 400 x 130 |
19
x 20 x 5.2
485 x 508 x 130
|
| Weight
lbs/kg (net) |
38
/ 17.3 |
44
/ 20 |
55
/ 25 |
61.6
/ 28 |
70.4
/ 32 |
|
| |
 |
|
|
|
230
V Model Specifications |
| |
|
|
|
|
| GENERAL |
|
| Rated
Capacity: |
700VA,
1000 VA, 1500 VA, 2000 VA, 3000 VA with a power factor
of 0.7 |
| Technology: |
True
on-line, double conversion topology with integral automatic
bypass |
| INPUT |
|
| Phase:
|
Single
phase plus ground |
| Input
Voltage Range: |
208V:
152-260V, 220V: 160-276V, 230V: 167-280V, 240V: 174-280V |
| Input
Power factor: |
0.98 |
| Frequency: |
50
/ 60 Hz Auto sensing |
| AC
Frequency range: |
45
- 65 Hz |
| Synchronization
range: |
±
3Hz |
| Input
Current (230V): |
700VA
- 3A, 1000VA - 4.4A, 1500VA - 6.5A, 2000VA - 8.7A, 3000VA
- 13A |
| Input
Protection: |
Circuit
Breaker for overload and short protection |
| DC
Bus Voltage: |
700VA
- 24V, 1000VA - 36V, 1500VA - 48V, 2000VA - 72V, 3000VA
- 96V |
| OUPUT |
|
| Output
Voltage: |
208
/ 220 / 230 / 240 VAC |
| Voltage
regulation: |
±
2% (700VA - 2000VA) ± 3% (3000VA) |
| Voltage
distortion: |
<
5% THD with non-linear loads, < 3% THD with linear
loads |
| Frequency
regulation: |
±
0.25 Hz (while on battery) |
| Dynamic
response: |
±
9 % max from 100% to 20 % or from 20% to 100 % linear
load |
| Overload
capacity: |
105%
for 10 seconds, 130% ± 10% for 300 msec |
| Efficiency
(Bypass Mode): |
Greater
than 95% |
| Efficiency
(On-line Mode): |
Greater
than 88% |
| Crest
Factor: |
3
: 1 |
| 230
V TOWER MODELS |
Capacity |
740VA
/490 W |
1000VA
/ 700 W |
1500VA
/ 1050 W |
2000VA
/ 1400 W |
3000VA
/ 2100 W |
| Input
Connection |
IEC
320 (10A) |
IEC
320 (16A) |
| Output
Connection Options |
4
x IEC 320 (10A) |
8
x IEC 320 (10A) |
|
4x
NEMA 5-15R |
8
x NEMA 5-15 R
|
2
x European |
6
x European |
| Battery
Type & Rating |
Sealed,
lead-acid
7.2Ah/12V |
Sealed,
lead-acid
7.2Ah/12V |
Sealed,
lead-acid
7.2Ah/12V |
Sealed,
lead-acid
7.2Ah/12V |
Sealed,
lead-acid
7.2Ah/12V |
| Battery
Quantity |
2 |
3 |
4 |
6 |
8 |
| Backup
Time (full load) |
6
min |
8
min |
7
min |
8
min |
7
min |
| Recharge
Time |
<8
hours to 90 % |
Dimensions
ins/mm
W x D x H |
5.7
x 15.8 x 8.7
145 x 400 x 220 |
7.7
x 18.5 x 15.2
195 x 470 x 385
|
| Weight
lbs/kg (net) |
27.5
/ 12.5 |
33
/ 15 |
39.6
/ 18 |
70.4
/ 32 |
81.4
/ 37 |
| 230
V 19" RACK-MOUNT MODELS (3U) |
Capacity |
740VA
/490 W |
1000VA
/ 700 W |
1500VA
/ 1050 W |
2000VA
/ 1400 W |
3000VA
/ 2100 W |
| Input
Connection |
IEC
320 (10A) |
IEC
320 (16A) |
| Output
Connection Options |
4
x IEC 320 (10A) |
8
x IEC 320 (10A) |
|
4x
NEMA 5-15R |
8
x NEMA 5-15 R
|
2
x European |
6
x European, 1 x IEC 320 (16A) |
| Battery
Type & Rating |
Sealed,
lead-acid
7.2Ah/12V |
Sealed,
lead-acid
7.2Ah/12V |
Sealed,
lead-acid
7.2Ah/12V |
Sealed,
lead-acid
7.2Ah/12V |
Sealed,
lead-acid
7.2Ah/12V |
| Battery
Quantity |
2 |
3 |
4 |
6 |
8 |
| Backup
Time (full load) |
6
min |
8
min |
7
min |
8
min |
7
min |
| Recharge
Time |
<8
hours to 90 % |
Dimensions
ins/mm
W x D x H |
19
x 15.8 x 5.2
485 x 400 x 130 |
19
x 20 x 5.2
485 x 508 x 130
|
| Weight
lbs/kg (net) |
38
/ 17.3 |
44
/ 20 |
55
/ 25 |
61.6
/ 28 |
70.4
/ 32 |
|
| |
 |
|
|
|
All
Models |
| |
| ALARMS
AND INDICATORS |
| Battery
Backup: |
Slow
beeping tone (approx. 0.25Hz) |
| Battery
Low: |
Rapid
beeping tone (approx. 1.00Hz) |
| Overload: |
Continuous
Tone |
| Front
Panel Display: |
High
Intensity LCD panel |
| Display
Parameters: |
Input
voltage, Output voltage, Input Frequency, Output Frequency, |
| |
Load
(%), Internal Temperature (°C) |
| Communication
(std): |
RS-232
bi-directional communication port and solid state signaling |
| (optional): |
Internal
SNMP/WEB Card for monitoring & control on network
or internet |
| STANDARDS |
| Safety:
|
EN50091-1-1 |
| Emissions: |
EN50091-2
class B |
| Immunity: |
EN50091-2 |
| Conformity: |
UL
1778, cUL 107.1, 107.2, (120V models), CE (230V Models) |
| Transient
Immunity (120V): |
Per
IEEE 62.41 (formerly IEEE 587) |
| Transient
Immunity (230V): |
Per
IEEE C 61000-4-5 level 3 |
| ENVIRONMENTAL |
| Ambient
temperature range: |
+32
°F to +104°F (+0 °C to +40 °C) |
| Optimum
temperature range: |
+59
°F to +77°F (+15 °C to +25 °C) |
| Storage
temperature: |
+5
°F to +122°F (-15 °C to +50 °C) |
| Cooling: |
Forced
air cooling |
| Humidity::
|
0-95%,
non-condensing |
| Elevation:
|
10,000
feet max (operation), 45,000 feet (storage) |
| Audible
noise: |
<
45 db normal and battery mode (700-1000 VA models)
< 52 db normal and battery mode (1500-3000 VA models) |
| MODEL
& PART NUMBER DESIGNATION |
| 120V
Tower Models: |
ATWS-0700-01,
ATWS-1000-01, ATWS-1500-01, ATWS-2000-01, ATWS-3000-01 |
| 230V
Tower Models: |
ATWS-0700-02,
ATWS-1000-02, ATWS-1500-02, ATWS-2000-02, ATWS-3000-02 |
| 120V
Rack-Tower Models: |
ARMS-1000-01,
ARMS-1500-01, ARMS-2000-01, ARMS-3000-01 |
| 230V
Rack-Tower Models: |
ARMS-1000-02,
ARMS-1500-02, ARMS-2000-02, ARMS-3000-02 |
|
 |
 |
 |
 |
 |
|