Tower
Model Specifications |
| |
| GENERAL |
|
| Rated
Capacity: |
425VA,
525 VA, 625 VA, 800VA, 1000 VA, 1200 VA, 1500VA, 2200VA |
| Technology: |
Line-interactive
topology with simulated sinewave output on battery |
| INPUT |
|
| Phase:
|
Single
phase plus ground |
| nput
Voltages: |
110V,
115V, 120V or 220V, 230V, 240V |
| Input
Voltage Range: |
±
25% |
| Frequency: |
50
/ 60 Hz Auto sensing |
| AC
Frequency range: |
45
- 65 Hz |
| nput
Current (120V): |
425-3.5A,
525-4.4A, 625-5.2A, 800-6.7A, 1000-8.3A, 1200-10A,
1500-12.5A, 2200-18.3A |
| Input
Current (230V): |
425-1.8A,
525-2.3A, 625-2.7A, 800-3.5A, 1000-4.3A, 1200-5.2A,
1500-6.5A, 2200-9.6A |
| Input
Protection: |
Fuse
or circuit breaker for overload and short circuit
(model dependent) |
| DC
Bus Voltage: |
425VA
~ 625VA - 12V, 800VA ~ 1500VA - 24V, 2200VA - 48V |
| OUPUT |
|
| Output
Voltage: |
110V,
115V, 120V or 220V, 230V, 240V |
| Voltage
regulation: |
±
5% (425VA - 2200VA) |
| Power
Factor : |
0.6 |
| Frequency
regulation: |
±
1% (while on battery) |
| Automatic
Voltage Regulation: |
Increases
or decreases output voltage by 15% if the input voltage
decreases
or increases by between 9% and 25% |
| Transfer
Time |
Between
2 and 4 milliseconds including detection time |
| Efficiency
(Standby Mode): |
Greater
than 95% |
| Overload
Capacity : |
110%
for 60 seconds, 130% for 3 seconds |
| TOWER
MODELS |
| Capacity |
425VA
/ 255 W |
525VA
/ 315 W |
625VA
/ 375 W |
800VA
/ 480 W |
| Input
Connection |
Fixed
power cord |
Removable
IEC cord |
| Output
Connection |
6
x NEMA 5-15R (3 backed-up and 3 surge only) |
5
x NEMA 5-15 R
|
| Battery
Type & Rating |
Sealed,
lead-acid
7.2Ah/12V |
Sealed,
lead-acid
7.2Ah/12V |
Sealed,
lead-acid
7.2Ah/12V |
Sealed,
lead-acid
7.2Ah/12V |
| Battery
Quantity |
1 |
1 |
1 |
3 |
| Backup
Time (full load) |
4
min |
4
min |
4
min |
7
min |
| Recharge
Time |
<4
hours to 90 % |
Dimensions
ins/mm
W x D x H |
3.8
x 12.6 x 5.3
97 x 320 x 135 |
5.1
x 15 x 7.9
130 x 382 x 201
|
| Weight
lbs/kg (net) |
12.8
/ 5.8 |
13.7
/ 6.2 |
14.3
/ 6.5 |
28.6
/ 13 |
| TOWER
MODELS |
| Capacity |
1000VA
/ 600 W |
1200VA
/ 720 W |
1500VA
/ 900 W |
2200VA
/ 1320 W |
| Input
Connection |
Removable
IEC cord |
Fixed
power cord |
| Output
Connection |
5
x NEMA 5-15 R
|
6
x NEMA 5-15R
|
| Battery
Type & Rating |
Sealed,
lead-acid
7.2Ah/12V |
Sealed,
lead-acid
7.2Ah/12V |
Sealed,
lead-acid
7.2Ah/12V |
Sealed,
lead-acid
7.2Ah/12V |
| Battery
Quantity |
2 |
2 |
2 |
4 |
| Backup
Time (full load) |
6
min |
5
min |
4
min |
6
min |
| Recharge
Time |
<6
hours to 90 % |
Dimensions
ins/mm
W x D x H |
5.1
x 15 x 7.9
130 x 382 x 201
|
6.7
x 17.6 x 8.4
170 x 448 x 214
|
| Weight
lbs/kg (net) |
33
/ 15 |
33.4
/ 15.2 |
34.3
/ 15.6 |
66
/ 30 |
|
| |
 |
|
|
|
19"
Rack-Mount Model Specifications |
| |
|
|
|
|
| GENERAL |
|
| Rated
Capacity: |
1000
VA, 1500 VA, 2200 VA |
| Technology: |
Line-interactive
topology with simulated sinewave output on battery |
| INPUT |
|
| Phase:
|
Single
phase plus ground |
| nput
Voltages: |
110V,
115V, 120V or 220V, 230V, 240V |
| Input
Voltage Range: |
±
25% |
| Frequency: |
50
/ 60 Hz Auto sensing |
| AC
Frequency range: |
45
- 65 Hz |
| nput
Current (120V): |
1000VA
- 8.3A, 1500VA - 12.5A, 2200VA - 18.3A |
| Input
Current (230V): |
1000VA
- 4.3A, 1500VA - 6.5A, 2200VA - 9.6A |
| Input
Protection: |
Fuse
or circuit breaker for overload and short circuit
(model dependent) |
| DC
Bus Voltage: |
1000VA
- 18V, 1500VA - 24V, 2200VA - 48V |
| OUPUT |
|
| Output
Voltage: |
110V,
115V, 120V or 220V, 230V, 240V |
| Voltage
regulation: |
±
5% (1000VA - 2200VA) |
| Power
Factor : |
0.6 |
| Frequency
regulation: |
±
1% (while on battery) |
| Automatic
Voltage Regulation: |
Increases
or decreases output voltage by 15% if the input voltage
decreases or increases by between 9% and 25% |
| Transfer
Time |
Between
4 and 8milliseconds including detection time |
| Efficiency
(Standby Mode): |
Greater
than 95% |
| Overload
Capacity : |
110%
for 60 seconds, 130% for 3 seconds |
| 19"
RACK-MOUNT MODELS |
| Capacity |
600VA
/ 360 W |
1000VA
/ 600 W |
1500VA
/ 900 W |
2200VA
/ 1320 W |
| Input
Connection |
Removable
IEC cord |
Fixed
power cord |
| Output
Connection |
5
x NEMA 5-15 R |
6
x NEMA 5-15R
|
| Battery
Type & Rating |
Sealed,
lead-acid
7.2Ah/6V |
Sealed,
lead-acid
8.0 Ah/6V |
Sealed,
lead-acid
8.5 Ah/6V |
Sealed,
lead-acid
7.2Ah/12V |
| Battery
Quantity |
2 |
2 |
2 |
4 |
| Backup
Time (full load) |
4
min |
5
min |
5
min |
6
min |
| Recharge
Time |
<8
hours to 90 % |
Dimensions
ins/mm
W x D x H |
19
x 14.3 x 1.73
483 x 362x 44
|
19
x 14 x 3.3
483 x 357x 84
|
19
x 13.8 x 5.1
483 x 351x 130
|
| Weight
lbs/kg (net) |
20.5
/ 9.4 |
25.3
/ 11.5 |
35.9
/ 16.3 |
62.6
/ 28.4 |
|
| |
 |
|
|
|
All
Models |
| |
| ALARMS
AND INDICATORS |
| Battery
Backup: |
Slow
beeping tone (approx. 0.25Hz) |
| Battery
Low: |
Rapid
beeping tone (approx. 1.00Hz) |
| Overload: |
Continuous
Tone |
| Front
Panel Display: |
LED's |
| LED
Display Parameters: |
On
Line (AC normal), On Battery (AC failure), Battery Fault
(425VA ~ 625VA models) |
| |
On
Line (AC normal), On Battery (AC failure), Battery Fault,
AVR Boost, AVR Buck (800VA ~ 2200VA models) |
| Communication
(std): |
RS-232
communication port and solid state signaling or USB |
| (optional): |
SNMP/WEB
card or module for monitoring and control on a network
or the internet |
| STANDARDS |
| Safety:
|
EN50091-1-1 |
| Emissions: |
EN50091-2
class B |
| Immunity: |
EN50091-2 |
| Conformity: |
UL
1778, cUL 107.1, 107.2, (120V models), CE (230V Models) |
| Transient
Immunity (120V): |
Per
IEEE 62.41 (formerly IEEE 587) |
| Transient
Immunity (230V): |
Per
IEEE C 61000-4-5 level 3 |
| ENVIRONMENTAL |
| Ambient
temperature range: |
+32
°F to +104°F (+0 °C to +40 °C) |
| Optimum
temperature range: |
+59
°F to +77°F (+15 °C to +25 °C) |
| Storage
temperature: |
+5
°F to +122°F (-15 °C to +50 °C) |
| Cooling: |
Natural
convection (425VA ~ 800VA), Forced air (1000VA ~ 2200VA) |
| Humidity::
|
0-95%,
non-condensing |
| Elevation:
|
10,000
feet max (operation), 45,000 feet (storage) |
| Audible
noise: |
<
40 db normal and battery mode (All models) |
| MODEL
& PART NUMBER DESIGNATION |
| 120V
Tower Models: |
STWS-0425-01,
STWS-0525-01, STWS-0625-01, STWS-0800-01, STWS-1000-01,
STWS-1200-01, STWS-1500-01, STWS-2200-01 |
| 230V
Tower Models: |
STWS-0425-02,
STWS-0525-02, STWS-0625-02, STWS-0800-02, STWS-1000-02,
STWS-1200-02, STWS-1500-02, STWS-2200-02 |
| 120V
Rack-Mount Models: |
SRMS-1000-01,
SRMS-1500-01, SRMS-2200-01 |
| 230V
Rack-Mount Models: |
SRMS-1000-02,