Standard
Run-Time Model Specifications |
| |
| GENERAL |
|
| Rated
Capacity: |
600VA,
1000 VA, 1500 VA, 2000 VA, 3000 VA with a power factor
of 0.6 |
| Technology: |
Line-interactive
topology with true sine wave output on battery |
| INPUT |
|
| Phase:
|
Single
phase plus ground |
| Input
Voltages: |
110V,
115V, 120V or 220V, 230V, 240V |
| Input
Voltage Range: |
±
25% |
| Frequency: |
50
/ 60 Hz Auto sensing |
| AC
Frequency range: |
45
- 65 Hz |
| Input
Current (120V): |
600VA
- 5A, 1000VA -8.2A, 1500VA -12.4A, 2000VA -16.5A,
3000VA -25A |
| Input
Current (230V): |
600VA
- 2.6A, 1000VA - 4.4A, 1500VA - 6.5A, 2000VA - 8.7A,
3000VA - 13A |
| Input
Protection: |
Fuse
or circuit breaker for overload and short circuit
(model dependent) |
| DC
Bus Voltage: |
600VA
- 24V, 1000VA - 24V, 1500VA - 36V, 2000VA - 48V, 3000VA
- 96V |
| OUPUT |
|
| Output
Voltage: |
110V,
115V, 120V or 220V, 230V, 240V |
| Voltage
regulation: |
±
5% (600VA - 3000VA) |
| Voltage
distortion: |
<
5% THD with non-linear loads, < 3% THD with linear
loads |
| Frequency
regulation: |
±
0.5% (while on battery) |
| Automatic
Voltage Regulation |
Increases
or decreases output voltage by 15% if the input voltage
decreases
or increases by between 9% and 25% |
| Transfer
Time |
Between
4 and 8 milliseconds including detection time |
| Efficiency
(Standby Mode): |
Greater
than 95% |
| Overload
Capacity |
110%
for 20 seconds, 125% for 5 seconds |
| Standard
Run-Time Tower Models |
Capacity |
600VA
/360 W |
1000VA
/ 600W |
1500VA
/ 900W |
2000VA
/ 1200WA |
3000VA
/ 1800W |
| Input
Connection |
Fixed
power cord
|
Hardwire
Terminals |
| Output
Connection |
4x
NEMA 5-15R |
6x
NEMA 5-15R |
H/W
+
4 x NEMA |
| Battery
Type & Rating |
Sealed,
lead-acid
7.2Ah/12V |
Sealed,
lead-acid
7.2Ah/12V |
Sealed,
lead-acid
7.2Ah/12V |
Sealed,
lead-acid
7.2Ah/12V |
Sealed,
lead-acid
7.2Ah/12V |
| Battery
Quantity |
2 |
2 |
3 |
4 |
8 |
| Backup
Time (full load) |
9
min |
5
min |
5
min |
5
min |
5
min |
| Recharge
Time |
<4
hours to 90 % |
Dimensions
ins/mm
W x D x H |
5.6
x 17.2 x 8.3
140 x 436 x 210 |
6.7
x 17.8 x 8.9
170 x 450 x 226
|
| Weight
lbs/kg (net) |
31
/ 14 |
33
/ 15 |
56
/ 25 |
66
/ 30 |
20
/ 44 |
| Standard
Run-Time 19" Rack-mount Models (3U) |
Capacity |
600VA
/360 W |
1000VA
/ 600W |
1500VA
/ 900W |
2000VA
/ 1200WA |
| Input
Connection |
Removable
IEC power cord or fixed power cord
|
| Output
Connection |
4
x NEMA 5-15 R |
| Battery
Type & Rating |
Sealed,
lead-acid
7.2Ah/12V |
Sealed,
lead-acid
7.2Ah/12V |
Sealed,
lead-acid
7.2Ah/12V |
Sealed,
lead-acid
7.2Ah/12V |
| Battery
Quantity |
2 |
2 |
3 |
4 |
| Backup
Time (full load) |
9
min |
5
min |
5
min |
5
min |
| Recharge
Time |
<8
hours to 90 % |
Dimensions
ins/mm
W x D x H |
19
x 15 x 5.2
485 x 381 x 130
|
| Weight
lbs/kg (net) |
38
/ 17.3 |
44
/ 20 |
55
/ 25 |
61.6
/ 28 |
| Standard
Run-Time 19" Rack-mount Models (2U) |
Capacity |
600VA
/360 W |
1000VA
/ 600W |
1500VA
/ 900W |
2000VA
/ 1200WA |
| Input
Connection |
Removable
IEC power cord or fixed power cord
|
| Output
Connection |
6
x NEMA 5-15 R |
| Battery
Type & Rating |
Sealed,
lead-acid
7.2Ah/12V |
Sealed,
lead-acid
7.2Ah/12V |
Sealed,
lead-acid
7.2Ah/12V |
Sealed,
lead-acid
7.2Ah/12V |
| Battery
Quantity |
2 |
2 |
3 |
4 |
| Backup
Time (full load) |
9
min |
5
min |
5
min |
5
min |
| Recharge
Time |
<8
hours to 90 % |
Dimensions
ins/mm
W x D x H |
19
x 16.9 x 3.3
485 x 430 x 84
|
19
x 24.2 x 3.3
485 x 615 x 84
|
| Weight
lbs/kg (net) |
38
/ 17.3 |
44
/ 20 |
55
/ 25 |
95
/ 43.2 |
|
| |
 |
|
|
|
Extended
Run-Time Model Specifications |
| |
|
|
|
|
| GENERAL |
|
| Rated
Capacity: |
1000
VA, 1500 VA, 2000 VA, 3000 VA with a power factor of
0.6 |
| Technology: |
Line-interactive
topology with true sine wave output on battery |
| INPUT |
|
| Phase:
|
Single
phase plus ground |
| Input
Voltages: |
110V,
115V, 120V or 220V, 230V, 240V |
| Input
Voltage Range: |
±
25% |
| Frequency: |
50
/ 60 Hz Auto sensing |
| AC
Frequency range: |
45
- 65 Hz |
| Input
Current (120V): |
1000VA
-8.2A, 1500VA -12.4A, 2000VA -16.5A, 3000VA -25A |
| Input
Current (230V): |
1000VA
- 4.4A, 1500VA - 6.5A, 2000VA - 8.7A, 3000VA - 13A |
| Input
Protection: |
Fuse
or circuit breaker for overload and short circuit
(model dependent) |
| DC
Bus Voltage: |
1000VA
- 24V, 1500VA - 36V, 2000VA - 48V, 3000VA - 48V |
| OUPUT |
|
| Output
Voltage: |
110V,
115V, 120V or 220V, 230V, 240V |
| Voltage
regulation: |
±
5% (1000VA - 3000VA) |
| Voltage
distortion: |
<
5% THD with non-linear loads, < 3% THD with linear
loads |
| Frequency
regulation: |
±
0.5% (while on battery) |
| Automatic
Voltage Regulation |
Increases
or decreases output voltage by 15% if the input voltage
decreases
or increases by between 9% and 25% |
| Transfer
Time |
Between
4 and 8 milliseconds including detection time |
| Efficiency
(Standby Mode): |
Greater
than 95% |
| Overload
Capacity |
110%
for 20 seconds, 125% for 5 seconds |
| Extended
Run-Time Tower Models |
Capacity |
1000VA
/ 600W |
1500VA
/ 900W |
2000VA
/ 1200WA |
3000VA
/ 1800W |
| Input
Connection |
Fixed
power cord
|
Hardwire
Terminals |
| Output
Connection |
6
x NEMA 5-15R |
H/W
+
6 x NEMA 5-15R |
| Battery
Type & Rating |
Sealed,
lead-acid
7.2Ah/12V |
Sealed,
lead-acid
17Ah/12V |
Sealed,
lead-acid
17Ah/12V |
Sealed,
lead-acid
17Ah/12V |
| Battery
Quantity |
4 |
3 |
4 |
4 |
| Backup
Time (full load) |
10
min |
15
min |
15
min |
10
min |
| Recharge
Time |
4
- 8 hours to 90 % depending on variable charger setting |
Dimensions
ins/mm
W x D x H |
6.7
x 17.7 x 8.8
170 x 450 x 224
|
6.7
x 18.9 x 16.9
170 x 480 x 430
|
6.7
x 21.6 x 16.9
170 x 550 x 430
|
| Weight
lbs/kg (net) |
50
/ 22.7 |
90
/ 41 |
110
/ 50 |
125
/ 57 |
| Extended
Run-Time 19" Rack-mount Models |
Capacity |
1000VA
/ 600W |
1500VA
/ 900W |
2000VA
/ 1200WA |
3000VA
/ 1800W |
| Input
Connection |
Fixed
power cord
|
Hardwire
Terminals |
| Output
Connection |
4
x NEMA 5-15R |
H/W
+
6 x NEMA 5-15R |
| Battery
Type & Rating |
Sealed,
lead-acid
7.2Ah/12V |
Sealed,
lead-acid
8.5Ah/12V |
Sealed,
lead-acid
8.5Ah/12V |
Sealed,
lead-acid
12Ah/12V |
| Battery
Quantity |
4 |
3 |
4 |
4 |
| Backup
Time (full load) |
10
min |
8
min |
8
min |
7
min |
| Recharge
Time |
4
- 8 hours to 90 % depending on variable charger setting |
Dimensions
ins/mm
W x D x H |
19
x 22 x 5.2
485 x 560 x 130
|
19
x 22 x 7
485 x 560 x 178
|
| Weight
lbs/kg (net) |
52
/ 24 |
61
/ 28 |
69
/ 32 |
113
/ 51 |
|
| |
 |
|
|
|
All
Models |
| |
| ALARMS
AND INDICATORS |
| Battery
Backup: |
Slow
beeping tone (approx. 0.25Hz) |
| Battery
Low: |
Rapid
beeping tone (approx. 1.00Hz) |
| Overload: |
Continuous
Tone |
| Front
Panel Display: |
LED
on standard runtime models and LED or LCD on extended
runtime models |
| Display
Parameters: |
Input
voltage, Output voltage, Input Frequency, Output Frequency, |
| |
Load
(%), Internal Temperature (°C) |
| Communication
(std): |
RS-232
bi-directional communication port and solid state signaling |
| (optional): |
SNMP/WEB
card or module for monitoring and control on a network
or the internet |
| STANDARDS |
| Safety:
|
EN50091-1-1 |
| Emissions: |
EN50091-2
class B |
| Immunity: |
EN50091-2 |
| Conformity: |
UL
1778, cUL 107.1, 107.2, (120V models), CE (230V Models) |
| Transient
Immunity (120V): |
Per
IEEE 62.41 (formerly IEEE 587) |
| Transient
Immunity (230V): |
Per
IEEE C 61000-4-5 level 3 |
| ENVIRONMENTAL |
| Ambient
temperature range: |
+32
°F to +104°F (+0 °C to +40 °C) |
| Optimum
temperature range: |
+59
°F to +77°F (+15 °C to +25 °C) |
| Storage
temperature: |
+5
°F to +122°F (-15 °C to +50 °C) |
| Cooling: |
Forced
air cooling |
| Humidity::
|
0-95%,
non-condensing |
| Elevation:
|
10,000
feet max (operation), 45,000 feet (storage) |
| Audible
noise: |
<
40 db normal and battery mode (600-1000 VA models)
< 45 db normal and battery mode (1500-3000 VA models) |
| MODEL
& PART NUMBER DESIGNATION - Standard Run-Time Models |
| 120V
Tower Models: |
TTWS-0600-01,
TTWS-1000-01, TTWS-1500-01, TTWS-2000-01, TTWS-3000-01 |
| 230V
Tower Models: |
TTWS-0600-02,
TTWS-1000-02, TTWS-1500-02, TTWS-2000-02, TTWS-3000-02 |
| 120V
Rack-Mount Models: |
TRMS-0600-01,
TRMS-1000-01, TRMS-1500-01, TRMS-2000-01 |
| 230V
Rack-Mount Models: |
TRMS-0600-02,
TRMS-1000-02, TRMS-1500-02, TRMS-2000-02 |
| MODEL
& PART NUMBER DESIGNATION - Extended Run-Time Models |
| 120V
Tower Models: |
TTWE-1000-01,
TTWE-1500-01, TTWE-2000-01, TTWE-3000-01 |
| 230V
Tower Models: |
TTWE-1000-02,
TTWE-1500-02, TTWE-2000-02, TTWE-3000-02 |
| 120V
Rack-Mount Models: |
TRME-1000-01,
TRME-1500-01, TRME-2000-01, TRME-3000-01 |
| 230V
Rack-Mount Models: |
TRME-1000-02,
TRME-1500-02, TRME-2000-02, TRME-3000-02 |
|
 |
 |
 |
 |
 |
|