Traffic UPS Specifications - TRTC-2000N
     
ELECTRICAL
INPUT
Voltage Range, VAC 90 to 150 programmable
Default 100 to 130 +/- 2VAC
Frequency, Hz 60 +/- 3 Hz
Maximum Input Current, A 30 A (Resistive)
Inrush Current Load Dependent
Over current Protection Double pole single throw circuit breaker rated 30 A for input and output

DC bus 60 A breaker
Transient Suppression MOV transient suppression elements (>150 V)
Step Load Response (50% Load Charge) 1/2 Cycle Full Recovery (Full resistive load)
Short Circuit Protection 15 A Circuit Breaker
Battery String Voltage, VDC 48 (Four 12VDC Batteries)
OUTPUT
Apparent Power, VA 2000VA (Inverter Mode)
2000VA (Line Mode)
Active Power, W 1500 (Inverter Mode)
1500 (Line Mode)
Power Factor 0.75
Output Voltage, VAC

Line and Buck/Boost Mode

Inverter Mode
120 nominal


100-130 +/- 2 VAC (follows input voltage)

120 VAC +/- 5%
Frequency, Hz 60 +/- 0.4 Hz
Transformer Linear (non-isolated)
Output Waveform Sine Wave
Output Waveform THD <3% (Resistive Load)
Load Crest Factor 3:1 (Max)
Overload Capacity 110% for 3 min.
PERFORMANCE
Transfer Time
- Controller
- PTS
- TOTAL
4 to 10 ms
<30 ms
<65 ms
Efficiency, Line Mode >95% (Resistive Load)
Efficiency, Inverter Mode >80% (Resistive Load)
 
ENVIRONMENTAL
Operating Temp °C
-37 to +74°C
(See Notes 1 & 2)
Storage Temp °C -50 to +75°C
Humidity <95% non-condensing
Altitude, ft (m) 10,000 (3000)
(See Note 2)
MECHANICAL
Dimensions
(WxDxH) inch/mm
W 17.5/444 - 19/483 w/flange
D 10.5/267
H 5.25/133 - 3 U
Weight (lb/kg) 46.2/21
Mounting 19" (483 mm) rak or shelf mount
Input Connection 3 Position Terminal Block
Output Connection to Loads Two 3 Position Terminal Blocks
Cooling
Microprocessor controlled, 12 VDC, 3.6" (92 mm) fan
Audible Noise Level, dBA <40
MBS/PTS Dimensions (WxDxH) inch/mm W 17.5/444 - 19/483 w/flange
D 8.5/216
H 3.5/89 - 2U
MBS/PTS Weight (lb/kg) 7.0/3.2
MBS/PTS Mounting Shelf or 19" rack mount
MBS/PTS Input Connection Terminal Block
MBS/PTS Output Connection to Loads Terminal Block
MBS/PTS Output Connection to UPS 6 foot cable ready for hard wire to UPS terminal block
MBS/PTS Cooling Convection (approx 7 W contractor coil dissipation)
CERTIFICATIONS AND APPROVALS
Electric Safety UL-1778, CSA-170.1, UL-1950
EMI FCC Class A
Surge Immunity Tested to: IEC 1000-4-5, IEEE C62.41

NOTES:

1. Between 55° and 74°C, the unit is de-rated to a maximum rectified-capacitive load of 1500VA / 1200W
2. De-rate operating temperature above 4900 ft (1500m) by 2°C per additional 1000 ft (300m)
 
FUNCTIONS 
Brownout Protection Unit boosts output voltage (or transfers to battery) during brownout or low input line conditions and returns to normal when input power stabilizes over user-selected time period.
Setpoints for Transfer / Retransfer, To / From Battery / Boost are users programmable.
Generator Compatibility Generator mode allows wider variation in input voltage and frequency for use with an AC generator
Battery Charger 10 A PFC switch-mode, two-stage charger, temperature compensated (-2.5 to -5 mV/°C/cell), auto shuttoff about 50°C
Inverter Mode Capable of running continuously in inverter mode
Inverter Mode Current Limit Continuous electronic current limit is provided
Remote Monitoring - Input and out put voltages
- Input line frequency
- Output power
- Battery voltage
- Battery temperature
CONTROL TERMINAL BLOCK
Functions

A. Provides 6 sets of programmable contacts at pin 1 thu pin 18 for intersection flash control, Remote Alarms, Pagers or other user interface.
1. "Low Batt": batteries have reached approximately 40% capacity remaining
2. "On Batt": unit is in inverter mode
3. "Timer": unit has been in inverter mode for 2 hours (programmable)
4. "Alarm": any of the following conditions occur:
a. Line Frequency error
b. Low Output voltage
c. No Temperature Probe
d. Overload
e. No battery connected
f. High temperature
g. Low temperature
5. "Fault": any of the following conditions occur:
a. Short circuit

b. Batt low voltage
c. Batt high voltage
d. High temperature
e. Overload
B. Provides 48 VDC signal to PTS on pins 21 & 22
C. Triggers self-test by momentarily shorting pin 19 & 20 with less than 100 ohm

Contact Type Form C. Dry contacts rated 1 Amp at 240 V
Wiring Uses 14-26 AWG
COMMUNICATIONS
RS-232/USB/Ethernet ports Monitors, controls with terminal emulation software
RS-232 DB-9, Female, Opto-Isolated, straight-thru cable
USB B-Type receptacle
Ethernet (Optional) 10/100 Mbps Ethernet, auto-detected
Display Panel 2-line LCD

NOTE: Specifications subject to change without notice.


Home l Applications l UPS Products l Services l How to Order l Discontinued Products
Customer Support l About Us l News & Events l Contact Us l Site Map


Marathon Power
tel: 310-689-2328 • fax: 310-689-2329


 
Traffic UPS
Specs.pdf


Traffic UPS
User Manual.pdf


Traffic UPS
Product Sheet.pdf





Download
Adobe
Acrobat




(Opens Adobe's
Web Site)

 
 
© 2003-2011. Marathon Power & Not Maurice, All Rights Reserved.