HomeApplications UPS Products ServicesHow to OrderCustomer SupportAbout UsNews & Events Contact Us












       
230 V Tower Model Specifications
 
GENERAL  
Rated Capacity: 6000 VA, 8000 VA, 10000 VA, 12000 VA with a power factor of 0.7
Technology: True on-line, double conversion topology with integral automatic bypass

INPUT  
Phase: Single phase plus ground
Input Bypass Voltage 184 - 265 VAC (+15% to -20% of 230 V nominal - user selectable)
Input Voltage Range: 120 / 140 / 160 / 180 VAC - 276 VAC (120V - 276V @ 25% load, 140V - 276V @ 50%, 160V - 276V @ 75% load, 180V - 276V @ 100% load)
Frequency: 50 / 60 Hz Auto sensing
AC Frequency range: 45 - 65 Hz
Synchronization range: ± 3Hz
Input Current: 6000VA - 23.0A, 8000VA - 30.7A, 10000VA - 38.3A, 12000VA - 46.0A
Input Power factor: 0.97

OUPUT  
Output Voltage: 208 / 220 / 230 / 240 VAC (user selectable)
Voltage regulation: ± 2%
Voltage distortion: < 5% THD with non-linear loads, < 3% THD with linear loads
Frequency regulation: ± 0.25 Hz (while on battery or in free run mode)
Dynamic response: ± 9 % max from 100% to 20 % or from 20% to 100 % linear load
Overload capacity: 100 - 125% for 1 min, 125 - 150 % for 10 sec
Efficiency (HE Mode): Greater than 95%
Efficiency (On-line Mode): Greater than 86%
Crest Factor: 3 : 1

ENVIRONMENTAL
Ambient temperature range: +32 °F to +104°F (+0 °C to +40 °C)
Optimum temperature range: +59 °F to +77°F (+15 °C to +25 °C)
Storage temperature: +5 °F to +122°F (-15 °C to +50 °C)
Cooling: Forced air cooling
Humidity:: 0-95%, non-condensing
Elevation: 10,000 feet max (operation), 45,000 feet (storage)
Audible noise: < 55 db normal and battery mode (600-8000 VA models)
< 55 db normal and battery mode (10000-12000 VA models)

STANDARDS
Safety: EN50091-1-1
Emissions: EN50091-2 class B
Immunity: EN50091-2
Conformity: UL 1778, CSA 107.1, 107.2, CE
Transient Immunity: Per IEEE C 61000-4-5 level 3

230V TOWER MODELS
Capacity
6000VA
/ 4200 W
8000VA
/ 5600W
10000VA
/ 7000W
12000VA
/ 8400W
Input Connection
Hardwire Terminal Block
Output Connection
Hardwire Terminal Block
Battery Type & Rating
Sealed, lead-acid
7.2Ah/12V
Sealed, lead-acid
7.2Ah/12V
Sealed, lead-acid
9 Ah/12V
Sealed, lead-acid
7.2Ah/12V
Battery Quantity
20
20
20
40
Backup Time (full load)
6 min
4 min
5 min
6 min
Recharge Time
<4 hours to 90 %
Dimensions ins/mm
W x D x H
10.2 x 27.6 x 27.6
258 x 700 x 700
10.1 x 27.2 x 28
257 x 690 x 715
13.5 x 27.2 x 34.6
342 x 690 x 878
Weight lbs/kg (net)
176 / 80
189 / 86
189 / 86
286 / 130

 

Home l Applications l UPS Products l Services
l How to Order
Customer Support l About Us l News & Events l Contact Us


Marathon Power
tel: 310-689-2328 • fax: 310-689-2329


 

Vault UPS Specs
6k-12k.pdf


Vault User
Manual
6k-12k.pdf


Vault 2U RM
5-in-1 Brackets.pdf


SNMP &
Web Card .pdf


AS-400
Relay Card.pdf


UPS Software
User Manual.pdf


Product
Registration.pdf


Product
Warranty.pdf


10 year
Pro-Rated
Warranty.pdf



Download
Adobe
Acrobat




(Opens Adobe's
Web Site)

 
 
© 2003-2010. Marathon Power & Not Maurice, All Rights Reserved.