Dimensions

(WxDxH) inch / mm

W 17.5 / 444 - 19 / 483 w/flange

D 10.5 / 267

H 5.25 / 133 - 3U


Weight (lb / kg)

46.2 / 21


Mounting

19" (483mm) rack or shelf mount


Input Connection

3 Position Terminal Blcok


Otput Connection to Leads

Two 3 Position Terminal Blocks


Cooling

Microprocessor controlled, 12VDC, 3.6" (92mm) fan


Audible Noise Level, dBA

less than 40


MBS/PTS Dimensions

(WxDxH) inch / mm

W 17.5 / 444 - 19 / 483 w/flange

D 18.5 / 216

H 3.5 / 89- 2 U


MBS / PTS Weight (lb / kg)

7.03 / 3.2


MBS / PTS Mounting

Shelf or 19" rack mount


MBS / PTS Input Connection

Terminal Block


MBS / PTS Output Connection

to Loads

Terminal Block


MBS / PTS Output Connection

to UPS

6 foot cable ready for hard wire to UPS terminal block


MBS / PTS Cooling

Convection (approx 7 W contractor coli dissipation)


CONTROL TERMINAL BLOCK

DESIGNED TO CONFORM TO

Functions

A. Provides 6 sets of programmable contacts at pin 1

    thu pin 18 for intersection flash control, remote alarms,

    pager or other user interface.

   1. "Low Batt": batteries have reached approx. 40%

        capacity remaining

   2. "On Batt": unit is in inverter mode

   3. "Timer": unit has been in inverter mode for 2 hours

        (programmable)

   4. "Alarm": any of the following conditions occur;

        a. Line Frequency Error

        b. Low Output Voltage

        c. No Temperature Probe

        d. Overload

        e. No Battery Connected

        f. High Temperature

        g. Low Temperature

    5. "Fault": any of the following conditions occur:

        a. Short Circuit

        b. Batt Low Voltage

        c. Batt High Voltage

        d. High Temperature

        e. Overload

B. Provides 48 VDC signal to PTS on pins 21 & 22

C. Triggers self-test by momentarily shorting pin 19 & 20         with less than ohm


Contact Type

Form C. Dry contacts rated 1 Amp at 240V


Wiring

Uses 14-26 AWG



Operating Temp °C

-37 to +74°C (See Notes)


Storage Temp °C

-50 to +75°C


Humidity

less than 95% non-condensing


Altitude, ft (m)

10,000 (3000) (See Note 2)



COMMUNICATIONS

Transfer Time

- Controller

- PTS

- TOTAL

.

4 to 10 ms

less than 30 ms

less than 65 ms


Efficiency, Line Mode

greater than 95% (Resistive Load)


Efficiency, Inverter Mode

greater than 80% (Resistive Load)



ENVIRONMENTAL

RS-232 / USB / Ethernet ports

Monitors, controls with terminal emulation software


RS-232

DB-9, Female, Opto-Isolated, Straight-thru cable


Ethernet (Optional)

10 / 100 Mbps Ethernet, Auto-detected


Display Panel

2-line LCD


USB

B-Type receptable



Notes:

1. Between 55° and 74°C, the unit is de-rated

     to a maximum rectified-capacitive load of

    1500VA / 1200W.


2. De-rate operating temperature above 4900

     ft. (1500m) by 2°C per additional 1000 ft.

    (300m).

Download Ruggedized Track specifications here.

ELECTRICAL PERFORMANCE

MECHANICAL

Electrical Safety

UL-1778, CSA-170.1, UL-1950


EMI

FCC Class A


Surge Immunity

Tested to: IEC 1000-4-5, IEEE C62.41



FUNCTIONS

Brownout Protection

Unit boosts output voltage (of transfers to battery) during brownout or low input line conditions and returns to normal when inout power stabilizes over user-selected time period. Setpoints for Transfer / Retransfer, To / From Battery / Boost are users programmable.


Generator Compatibility

Generator mode allows wider variation in input voltage and frequency for use with an AC generator.


Battery Charger 10 A

PFC switch-mode, two-stage charger, temperature compensated (-2.5 to -5 mV°/C/cell, auto shutoff about 50°C


Inverter Mode

Capable of running continuously in inverter mode


Inverter Mode Current Limit

Continuous electronic current limit is provided


Remote Monitoring

- Input and output voltages

- Input line frequency

- Output power

- Battery Voltage

- Battery Temperature


ELECTRICAL OUTPUT

Apparent Power, VA

2000 (Inverter Mode) 2000 (Line Mode)


Active Power, W

1500 (Inverter Mode) 1500 (Line Mode)


Power Factor

0.75


Output Voltage

VAC Linep

Buck/ Boost Mode Inverter Mode

120 nominal

100-130 +/- 2 VAC (follows input voltage)

120 VAC +/- 5%


Frequency, Hz

60 +/- 0.4 Hz


Transformer

Linear (non-isolated)


Output Waveform

Sine Wave


Output Waveform THD

less than 3% (Resistive Load)


Load Crest Factor

3:1 (Max)


Overload Capacity

110% for 3 min.


ELECTRICAL INPUT

Voltage Range, VAC

90 to 150 programmable – Default 100 to 130 +/- 2VAC


Frequency, Hz

60 +/- 3 Hz


Maximum Input Current, A

30 A (Resistive)


Inrush Current

Load Dependent


Over current Protection

Double pole single throw circuit breaker rated 30 A for input and output DC bus 60 A breaker


Transient Suppression

MOV transient suppression elements (>150 V)


Step Load Response (50% Load Charge)

1/2 Cycle Full Recovery (Full resistive load)


Short Circuit Protection

15 A Circuit Breaker


Battery String Voltage, VDC

48 (Four 12VDC Batteries)


Ruggedized Track UPS Specifications