Dimensions (WxDxH) inch / mm |
W 17.5 / 444 - 19 / 483 w/flange D 10.5 / 267 H 5.25 / 133 - 3U |
|
Weight (lb / kg) |
46.2 / 21 |
|
Mounting |
19" (483mm) rack or shelf mount |
|
Input Connection |
3 Position Terminal Blcok |
|
Otput Connection to Leads |
Two 3 Position Terminal Blocks |
|
Cooling |
Microprocessor controlled, 12VDC, 3.6" (92mm) fan |
|
Audible Noise Level, dBA |
less than 40 |
|
MBS/PTS Dimensions (WxDxH) inch / mm |
W 17.5 / 444 - 19 / 483 w/flange D 18.5 / 216 H 3.5 / 89- 2 U |
|
MBS / PTS Weight (lb / kg) |
7.03 / 3.2 |
|
MBS / PTS Mounting |
Shelf or 19" rack mount |
|
MBS / PTS Input Connection |
Terminal Block |
|
MBS / PTS Output Connection to Loads |
Terminal Block
|
|
MBS / PTS Output Connection to UPS |
6 foot cable ready for hard wire to UPS terminal block |
|
MBS / PTS Cooling |
Convection (approx 7 W contractor coli dissipation) |
Functions |
A. Provides 6 sets of programmable contacts at pin 1   thu pin 18 for intersection flash control, remote alarms,   pager or other user interface.   1. "Low Batt": batteries have reached approx. 40%     capacity remaining   2. "On Batt": unit is in inverter mode   3. "Timer": unit has been in inverter mode for 2 hours     (programmable)   4. "Alarm": any of the following conditions occur;     a. Line Frequency Error     b. Low Output Voltage     c. No Temperature Probe     d. Overload     e. No Battery Connected     f. High Temperature     g. Low Temperature
  5. "Fault": any of the following conditions occur:     a. Short Circuit     b. Batt Low Voltage     c. Batt High Voltage     d. High Temperature     e. Overload B. Provides 48 VDC signal to PTS on pins 21 & 22 C. Triggers self-test by momentarily shorting pin 19 & 20     with less than ohm |
|
Contact Type |
Form C. Dry contacts rated 1 Amp at 240V |
|
Wiring |
Uses 14-26 AWG |
|
|
Operating Temp °C |
-37 to +74°C (See Notes)
|
|
Storage Temp °C |
-50 to +75°C
|
|
Humidity |
less than 95% non-condensing
|
|
Altitude, ft (m) |
10,000 (3000) (See Note 2)
|
|
Transfer Time - Controller - PTS - TOTAL |
. 4 to 10 msless than 30 ms less than 65 ms |
|
Efficiency, Line Mode |
greater than 95% (Resistive Load)
|
|
Efficiency, Inverter Mode |
greater than 80% (Resistive Load)
|
|
RS-232 / USB / Ethernet ports |
Monitors, controls with terminal emulation software |
|
RS-232 |
DB-9, Female, Opto-Isolated, Straight-thru cable
|
|
Ethernet (Optional) |
10 / 100 Mbps Ethernet, Auto-detected
|
|
Display Panel |
2-line LCD
|
|
USB |
B-Type receptable
|
|
Electrical Safety |
UL-1778, CSA-170.1, UL-1950 |
|
EMI |
FCC Class A
|
|
Surge Immunity |
Tested to: IEC 1000-4-5, IEEE C62.41
|
|
Apparent Power, VA |
2000 (Inverter Mode) 2000 (Line Mode) |
|
Active Power, W |
1500 (Inverter Mode) 1500 (Line Mode) |
|
Power Factor |
0.75 |
|
Output Voltage VAC Linep Buck/ Boost Mode Inverter Mode |
120 nominal 100-130 +/- 2 VAC (follows input voltage) 120 VAC +/- 5% |
|
Frequency, Hz |
60 +/- 0.4 Hz |
|
Transformer |
Linear (non-isolated) |
|
Output Waveform |
Sine Wave |
|
Output Waveform THD |
less than 3% (Resistive Load) |
|
Load Crest Factor |
3:1 (Max) |
|
Overload Capacity |
110% for 3 min. |
Voltage Range, VAC |
90 to 150 programmable – Default 100 to 130 +/- 2VAC |
|
Frequency, Hz |
60 +/- 3 Hz |
|
Maximum Input Current, A |
30 A (Resistive) |
|
Inrush Current |
Load Dependent |
|
Over current Protection |
Double pole single throw circuit breaker rated 30 A for input and output DC bus 60 A breaker |
|
Transient Suppression |
MOV transient suppression elements (>150 V) |
|
Step Load Response (50% Load Charge) |
1/2 Cycle Full Recovery (Full resistive load) |
|
Short Circuit Protection |
15 A Circuit Breaker |
|
Battery String Voltage, VDC |
48 (Four 12VDC Batteries) |
|
Notes:
1. Between 55° and 74°C, the unit is de-rated
to a maximum rectified-capacitive load of
1500VA / 1200W.
2. De-rate operating temperature above 4900
ft. (1500m) by 2°C per additional 1000 ft.
(300m).
Download Ruggedized Track specifications here.
Brownout Protection |
Unit boosts output voltage (of transfers to battery) during brownout or low input line conditions and returns to normal when inout power stabilizes over user-selected time period. Setpoints for Transfer / Retransfer, To / From Battery / Boost are users programmable. |
|
Generator Compatibility |
Generator mode allows wider variation in input voltage and frequency for use with an AC generator. |
|
Battery Charger 10 A |
PFC switch-mode, two-stage charger, temperature compensated (-2.5 to -5 mV°/C/cell, auto shutoff about 50°C |
|
Inverter Mode |
Capable of running continuously in inverter mode |
|
Inverter Mode Current Limit |
Continuous electronic current limit is provided |
|
Remote Monitoring |
- Input and output voltages - Input line frequency - Output power - Battery Voltage - Battery Temperature |
Copyright © 2015 - 2018 Marathon Power Inc. All rights reserved.