310.689.2328

Output Voltage

110 / 115 / 120 / 127 VAC


Voltage Regulation

+/-2%


Voltage Distortion

Greater than 5% THD with non-linear loads, greater than 3% THD with linear loads


Frequency Regulation

+/- 0.25 Hz (while on battery or in free run mode)


Dynamic Response

+/- 9% max from 100% to 20% or from 20% to 100% linear load


Overload Capacity

100 - 125% for 1 min, 125-150% for 10 sec


Efficiency

Greater than 93% (HE Mode), Greater than 88% (On-line Mode)


Crest Factor

3:1



Input (AC) Connection

Fixed power cord (std) or Hardwire Terminals (optional)


Output (AC) Connection

6 x NEMA 5-15R (std) or Hardwire Terminals (optional)


Dimensions in / mm W x D x H

6 x 16.5 x 9.4 / 152 x 420 x 238


Weight lbs / kg (net)

17 / 7.7, 19 / 8.6, 20 / 9


Operating Temperature Range

-40°C to +60°C / -40°F to 140°F


Phase

Single phase plus ground


Bypass Voltage

96 - 138 VAC (user selectable)


Input Voltage Range

60 / 70 / 80 VAC - 144 (60V @ 40%, 70V @ 70%,

80V @ 100% load)


Frequency

50 / 60 Hz Auto Sensing


AC Frequency Range

45 - 65 Hz


Input Current (120V)

5.8A / 8.2A / 12.4A


Input Power Factor

.97


GENERAL

Input (AC) Connection

Hardwire Terminals


Output (AC) Connection

Hardwire Terminals + 2 NEMA 5-15R Receptacles


Dimensions in / mm W x D x H

16.7 x 10 x 5.11 / 424 x 254 x 130


Weight lbs / kg (net)

15.5 / 7, 18.5 / 8.4, 20.5 / 9.3


Operating Temperature Range

-40°C to +60°C / -40°F to 140°F


Rack Mount Model Numbers

VRRN-0700-H1 / VRRN-1000-H1 / VRRN-1500-H1


Tower Model Numbers

VTRN-0700-C1 / VTRN-1000-C1 / VTRN-1500-C1


Rated Capacity

700VA / 490W, 1000VA / 700W, 1500VA / 1050W


Technology

True on-line, double conversion topology with integral automatic bypass


RACK MOUNT & TOWER SPECIFICATIONS

OUTPUT

RUGGEDIZED UPS

PHYSICAL (TOWER MODELS)

PHYSICAL (RACK MOUNT MODELS)

Ruggedized Vault UPS Specifications

INPUT

Download Ruggedized Vault  specifications here.

RACK MOUNT SPECIFICATIONS

Notes:

1. These units do not contain internal batteries.


2. An additional internal 5A charger is included

     in tower models.


3. Please contact us for estimated back-up 

     times using various batteries.