GENERAL

INPUT


Phase

Single phase plus ground


Input Voltages

110V, 115V, 120V or 220V, 230V, 240V


Input Voltage Range

± 25%


Frequency

50 / 60 Hz Auto sensing


AC Frequency range

45 – 65 Hz


Input Current (120V)

1000VA – 8.3A, 1500VA – 12.5A, 2200VA – 18.3A


Input Current (230V)

1000VA – 4.3A, 1500VA – 6.5A, 2200VA – 9.6A


Input Protection

Fuse or circuit breaker for overload and short circuit (model dependent)


DC Bus Voltage

1000VA – 18V, 1500VA – 24V, 2200VA – 48V

310.689.2328

120V 19" RACK-MOUNT MODELS

Model Number

SRMS-0600-01

SRMS-1000-01

SRMS-1500-01

SRMS-2200-01

Capacity

600VA / 360W

1000VA / 600W

1500VA / 900W

2200VA / 1320W

Input Connection

IEC C-14 Receptacle

Fixed NEMA 5-20P
power cord

Output Connection

5 x NEMA 5-15R Receptacle
(4 backed-up; 1 surge only)

4 x NEMA 5-15R Receptacle

Battery Type & Rating

Sealed,lead-acid 7.2Ah/12V

Sealed,lead-acid 8Ah/6V

Sealed,lead-acid 8.5Ah/6V

Sealed,lead-acid 7.2Ah/12V

Battery Quantity

2

3

2

4

Backup Time (full load)

4 min

5 min

6 min

Recharge Time

<8 hours to 90 %

Dimensions ins/mm
W x D x H

19 x 14.3 x 1.73
483 x 362x 44

19 x 14 x 3.3
483 x 357x 84

19 x 13.8 x 5.1
483 x 351x 130

Weight lbs/kg (net)

20.5 / 9.4

25.3 / 11.5

35.9 / 16.3

62.6 / 28.4

230V 19" RACK-MOUNT MODELS

Model Number

SRMS-0600-02

SRMS-1000-02

SRMS-1500-02

SRMS-2200-02

Capacity

600VA / 360W

1000VA / 600W

1500VA / 900W

2200VA / 1320W

Input Connection

IEC C-14 Receptacle

Fixed NEMA 5-20P
power cord

Output Connection

5 x NEMA 5-15R Receptacle
(4 backed-up; 1 surge only)

4 x NEMA 5-15R Receptacle

Battery Type & Rating

Sealed,lead-acid 7.2Ah/6V

Sealed,lead-acid 8Ah/6V

Sealed,lead-acid 8.5Ah/6V

Sealed,lead-acid 7.2Ah/12V

Battery Quantity

2

3

2

4

Backup Time (full load)

4 min

5 min

6 min

Recharge Time

<8 hours to 90 %

Dimensions ins/mm
W x D x H

19 x 14.3 x 1.73
483 x 362x 44

19 x 14 x 3.3
483 x 357x 84

19 x 13.8 x 5.1
483 x 351x 130

Weight lbs/kg (net)

20.5 / 9.4

25.3 / 11.5

35.9 / 16.3

62.6 / 28.4

OUTPUT


Output Voltage

110V, 115V, 120V or 220V, 230V, 240V


Voltage regulation

± 5% (425VA – 2200VA)


Power Factor

0.6


Frequency Regulation

± 1% (while on battery)


Automatic Voltage Regulation

Increases or decreases output voltage by 15% if the input voltage decreases or increases by between 9% and 25%


Transfer Time

Between 4 and 8 milliseconds including detection time


Efficiency (Standby Mode)

Greater than 95%


Overload Capacity

110% for 60 seconds, 130% for 3 seconds

Rated Capacity

1000VA, 1500VA, 2200VA


Technology

Line-interactive topology with simulated sinewave output on battery